Approval/Certificate/Document of Conformity
(13)
SCHEDULE
(14)
to Type Examination Certificate DEKRA 11ATEX0129 X Issue No. 3
Page 2/3
Form 244
Version 1 (2016-04)
(15)
Description
Power Control Unit, ACT20-FEED-IN-PRO-S and ACT20-FEED-IN-PRO-P are used to distribute
supply voltage to Power Rail Type CH20M-BUS on which it is mounted.
The Control Unit is connected to an external power supply and optionally to a backup power
supply.
The Control Unit detects errors from the modules mounted on the rail and provides a collective
status alarm via a potential free contact.
Ambient temperature range: -20
o
C to +60
o
C
Electrical data
Power Supply (terminals 51, 52): U = 21,6 ... 26,6 Vdc.
Backup Power Supply (terminals 53, 54): U = 21,6 ... 26,6 Vdc.
Power Rail (rear contacts): U = 21,6 ... 26,6 Vdc (with 40 V transient suppression)
Power Rail Status Relay (terminals 41, 42, 43): U ≤ 30 Vdc or 32 Vac, I ≤ 2 A.
If the Control Unit is installed outside the hazardous area, the following data for the relay contacts
apply:
U ≤ 30 Vdc or 250 Vac, I ≤ 2 A.
Installation instructions
The instructions provided with the product shall be followed in detail to assure safe operation.
(16)
Report
Number
No. NL/DEK/ExTR11.0047/02.
(17)
Speci
fic
conditions
of
use
The Power Control Unit shall be installed in an enclosure, in conformity with type of protection
Ex n or Ex e, providing a degree of protection of at least IP54.
Cable entry devices and blanking elements shall fulfill the same requirements.
(18)
Essential Health and Safety Requirements
Covered by the standards listed at item (9).
(19)
Test
documentation
As listed in Report No. NL/DEK/ExTR11.0047/02.