User Documentation

Weidmüller Interface GmbH Co. KG; Klingenbergstraße 16, 32758 Detmold-Germany
A3C 6
A3C 6 PE
550 V
36 A / ΔT
≤
40 K
34 A / ΔT
≤
40 K
0,6 mΩ
6 mm²
6 mm²
0,5 - 6 mm²
0,5 - 6 mm²
0,5 - 6 mm²
0,5 - 6 mm²
0,5 - 6 mm²
0,5 - 6 mm²
22 - 8 AWG
22 - 8 AWG
12 mm
12 mm
440 V
C - Adjacent – separated by an end plate no difference between one or two cross-connections
550 V
352 V
550 V
220 V
Application Case
- Rated current with ZQV
- Rated conductor cross section
- Conductor cross section flexible
- Contact resistance
with rated conductor, 6 mm²
- Conductor cross section stranded
- Conductor cross section solid
IECEx / ATEX Terminal and Cross-Connection Arrangements:
- cross section, American Wire Gauge
- Stripping length
- Rated current
- Rated voltage
Technical data according to IEC/EN 60079-7 (increased safety "eb"):
Information for further cross-connector arrangements will be provided on request.
D - Intermediate - bridging one or more unconnected terminals (e.g. every 3rd terminal) no difference
between one or two cross connections
F - Next to a protective conductor terminal (earth) with end plate
H - Cross-connection with twin parallel
Note:
If smaller cross sections than the rated cross section are used, the belonging lower current has to be laid
down in the IECEx/EC-Type Examination Certificate of the complete apparatus.
Max voltage data according to IEC/EN 60079-7 in conjunction with
protective earth terminal blocks of the A-Series, (increased safety "eb"):
A - Continuous no difference between one or two cross connections
Version: A3C 6; 10652161 Index: 03 Date: 07.2019
2