User Documentation

Weidmüller Interface GmbH Co. KG; Klingenbergstraße 16, 32758 Detmold-Germany
If smaller conductor cross sections than the rated conductor cross sections are used, then the corresponding
lower current shall be stated in the Certificate of the complete apparatus.
Manually cut cross connections and cross connections with blank ends (ZQV´s
≥ 20 poles) shall not
be used.
Essential Health and Safety Requirements:
Concerning ESRs this Schedule verifies compliance with the Annex III of ATEX directive only. By placing the
product on the market, the manufacturer declares compliance with other relevant Directives, and all other safety
related requirements including those of Annex II of this Directive.
No other wire sizes or types than the ones specified in instructions must be used. The terminal blocks must
either be mounted next to another block of the same type and size or with an end plate.
T6 (- 60°C ... +40 °C)
T5 (- 60°C … +55 °C)
T4 (- 60°C ... +70 °C)
The enclosure shall be constructed to block all sun and UV light from affecting the terminal blocks. The terminal
blocks shall be placed inside a suitable certified IP54 enclosure in type of protection “e” for gas atmosphere. For
dust atmosphere the terminal blocks shall be mounted inside a suitable certified enclosure (EN60079-31) in type
of protection “t”.
Under normal operating conditions the temperature rise of the terminal blocks is maximum 40 K, measured at
the maximum permitted rated current. Due to the above mentioned, the terminal blocks may be used in
apparatus of temperature classes T6..T1 as long as the terminal block ambient temperature range is not
exceeded. No part of terminal block must exceed 110 °C under any condition.
When using the types A3C 10 and A3C 10 PE especially with other terminal blocks series or sizes or
accessories the requirements for clearance and creepage distances according to table 1 of
EN 60079-7 must be observed. Regarding the use of covers, cross-connectors and end brackets the
instructions of the manufacturer must be followed.
For cross connection accessories, current rating, resistance across the terminal please refer to the table under
“Technical data” above.
Version: A3C 10; 12857787; Index: 01 Date: 06.2019