User Documentation

Weidmüller Interface GmbH Co. KG; Klingenbergstraße 16, 32758 Detmold-Germany
A2T 2.5 VL
A2T 2.5 PE
550 V
21 A / ΔT 40 K
20 A / ΔT 40 K
1,2 mΩ
2,5 mm²
2,5 mm²
0,5 - 2,5 mm²
0,5 - 2,5 mm²
0,5 - 2,5 mm²
0,5 - 2,5 mm²
0,5 - 2,5 mm²
0,5 - 2,5 mm²
28 - 12 AWG
28 - 12 AWG
10 mm
10 mm
352 V
352 V
550 V
176 V
352 V
352 V
176 V
D - Intermediate - bridging one or more unconnected terminals (e.g. every 3rd terminal) no difference
between one or two cross connections
- Conductor cross section solid
IECEx / ATEX Terminal and Cross-Connection Arrangements:
- Conductor cross section flexible
- cross section, American Wire Gauge
Max voltage data according to IEC/EN 60079-7 in conjunction with
protective earth terminal blocks of the A2T 2.5-Series, (increased safety "eb"):
- Stripping length
A - Continuous no difference between one or two cross connections
C - Adjacent – separated by an end plate no difference between one or two cross-connections
Application Case
E - Next to a protective conductor terminal (earth)
H - Cross-connection with twin parallel
Information for further cross-connector arrangements will be provided on request.
- Rated conductor cross section
- Conductor cross section stranded
- Contact resistance top level
with rated conductor, 2,5 mm²
- Contact resistance
with rated conductor, 2,5 mm²
- Rated voltage
T
echnical data according to IEC/EN 60079-7 (increased safety "eb"):
- Rated current with ZQV
- Rated current
Version: A2T 2.5 VL 10652178 Index: 03 Date: 05.2019
2