Datasheet

Data sheet...
TERMOPTO
TOS 24VDC/48VDC 0,5A
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Creation date November 19, 2012 2:24:26 PM CET
Catalogue status 06.11.2012 / We reserve the right to make technical changes. 2
Dimensions and weights
Width 6.1 mm
Height 74.5 mm
Depth 55 mm
Net weight 21 g
Temperatures
Operating temperature -20 °C...+60 °C
Storage temperature -40 °C...+80 °C
Probability of failure
MTTF 2,500 Years
Connection data
Clamping range, rated connection 2.5 mm²
Clamping range, rated connection, min. 0.5 mm²
Clamping range, rated connection, max. 4 mm²
Tightening torque, min. 0.4 Nm
Tightening torque, max. 0.6 Nm
Stripping length, rated connection 9 mm
Control side
Rated control voltage 24 V DC ±20 %
Nominal control current 7 mA DC
Power rating ≤ 170 mW
Input frequency < 200 Hz
Cut-in (switch-on) voltage ≥ 19.2 V DC
Dropout voltage ≤ 9.6 V DC
Protective circuit, control side Varistor, rev. polarity
protection
Status display on control side
Green LED
Load side
Rated switching voltage 5...48 V DC
Continuous current 500 mA
Rated switching current 500 mA
Switch-on delay < 20 µs
Switch-off delay < 200 µs
Load category DC1
Leakage current
< 10 µA
Protective circuit, load side Integrated free-wheel
diode
Voltage drop at max. load < 1 V
Load side status indicator
No
Short-circuit-proof No
General data
Solid-state type Transistor
No. of poles 1
Conductor connection system
Screw connection
Humidity 5...95 % rel. humidity
T
u
= 40 °C, no
condensation
UL 94 flammability rating
V-0
Standards DIN EN 50178, IEC
62314, UL508
Insulation coordination
Rated voltage
300 V
Clearance and creepage distances for
control side - load side > 3 mm
Impulse withstand voltage 4 kV (1.2/50 µs)
Pollution severity
2
Surge voltage category III
Further details of approvals
Standards DIN EN 50178, IEC
62314, UL508