User manual
6 Detailbeschreibungen I/O-Module | Kommunikationsmodul UR20-1COM-SAI-PRO
398 1432780000/08/12.2015Handbuch u-remote
Diagnosedaten UR20-1COM-SAI-PRO
Name Byte Bit Beschreibung Default
Fehlerindikator 0
0 Module error
1 Internal error
2 External error
3 Channel error 0
4 Error
5 Power supply fault 0
6 Reserved 0
7 Reserved
Modultyp 1
0
Module Type 0x05
1
1 0
2 1
3 0
4 Reserved 1
5 Reserved 0
6 Reserved 0
7 Reserved 0
Fehlerbyte 2 2 0 ... 7 Reserved 0
Fehlerbyte 3 3
0 ... 3 Reserved 0
4 Communication fault 0
5 Hot Plug 0
5 Reserved 0
7 New Subbus Diag 0
Kanaltyp 4
0
Channel type 0x79
1
1 0
2 0
3 1
4 1
5 1
6 1
7 0
Diagnosenbits
pro Kanal
5
Number of diagnostic bit per
channel
8
Anzahl Kanäle 6
Number of similar channels per
module
1
Kanalfehler
7 0 Error at channel 0 0
8 ... 10 1 ... 31 Reserved
Fehler Kanal 0 11
0 Subbus scanning
1 Subbus communication error
2 ... 5 Reserved
6 Subbus over current
7 Reserved
Fehler Kanal 1
...
Fehler Kanal 31
12
...
42
0 ... 7 Reserved 0
Zeitstempel 43-46 time stamp [µs] (32bit)