User manual

6 Detailbeschreibungen I/O-Module | Analoges Eingangsmodul UR20-4AI-TC-DIAG
299Handbuch u-remote1432780000/08/12.2015
Diagnosedaten UR20-4AI-TC-DIAG
Name Byte Bit Beschreibung Default
Fehlerindikator 0
0 Module error
1 Internal error
2 External error
3 Channel error
4 Error
5 Power supply fault
6 Reserved 0
7 Parameter error
Modultype 1
0
Module Type 0x05
1
2
3
4 Channel information available 1
5 Reserved 0
6 Reserved 0
7 Reserved 0
Fehlerbyte 2 2 0 ... 7 Reserved 0
Fehlerbyte 3 3
0..2 Reserved 0
3 Internal diagnostic FIFO full
4 Power supply fault
5 Reserved 0
6 Process alarm lost
7 Reserved 0
Kanaltyp 4
0..6 Channel type 0x71
7 Reserved 0
Diagnosenbits
pro Kanal
5
Number of diagnostic bit per
channel
8
Anzahl Kanäle 6
Number of similar channels per
module
4
Kanalfehler 7
0 Error at channel 0
1 Error at channel 1
2 Error at channel 2
3 Error at channel 3
4..7 Reserved 0
Kanalfehler 8 8..15 Reserved 0
Kanalfehler 9 16..23 Reserved 0
Kanalfehler 10 24..31 Reserved 0
Fehler Kanal 0 11
0 Parameter error
1 Reserved 0
2 Reserved 0
3 CJC error
4 Line break
5 Process alarm lost
6 Lower limit exceeded
7 Upper limit exceeded
Diagnosedaten UR20-4AI-TC-DIAG
Name Byte Bit Beschreibung Default
Fehler Kanal 1 12
0 Parameter error
1 Reserved 0
2 Reserved 0
3 CJC error
4 Line break
5 Process alarm lost
6 Lower limit exceeded
7 Upper limit exceeded
Fehler Kanal 2 13
0 Parameter error
1 Reserved 0
2 Reserved 0
3 CJC error
4 Line break
5 Process alarm lost
6 Lower limit exceeded
7 Upper limit exceeded
Fehler Kanal 3 14
0 Parameter error
1 Reserved 0
2 Reserved 0
3 CJC error
4 Line break
5 Process alarm lost
6 Lower limit exceeded
7 Upper limit exceeded
Fehler Kanal 4
...
Fehler Kanal 31
15 ... 42 0 ... 7 Reserved 0
Zeitstempel 43-46 time stamp [µs] (32bit)
Prozessdaten
1)
Eingänge UR20-4AI-TC-DIAG
Byte Format Beschreibung
IB0
Wort TC0
IB1
IB2
Wort TC1
IB3
IB4
Wort TC2
IB5
IB6
Wort TC3
IB7
1) Internes Prozessdatenmapping bei Datenformat „Standard“. Je nach Feld-
busspezifikation und Datenformateinstellung der kommunizierenden Feldbus-
komponenten können Bytes und/oder Wörter bei der Datenübertragung gedreht
werden.