User manual

6 Detailbeschreibungen I/O-Module | Analoges Eingangsmodul UR20-4AI-UI-16-DIAG
246 1432780000/08/12.2015Handbuch u-remote
Diagnosedaten UR20-4AI-UI-16-DIAG
Name Byte Bit Beschreibung Default
Fehlerindikator 0
0 Module error
1 Internal error
2 External error
3 Channel error
4 Error
5 Power supply fault
6 Reserved 0
7 Parameter error
Modultyp 1
0
Module type 0x05
1
2
3
4 Channel information available 1
5 Reserved 0
6 Reserved 0
7 Reserved 0
Fehlerbyte 2 2 0 ... 7 Reserved 0
Fehlerbyte 3 3
0 ... 2 Reserved 0
3 Internal diagnostic FIFO full
4 Power supply fault
5 ... 7 Reserved 0
Kanaltyp 4
0 ... 6 Channel type 0x74
7 Reserved 0
Diagnosenbits
pro Kanal
5
Number of diagnostic bit per
channel
8
Anzahl Kanäle 6
Number of similar channels per
module
4
Kanalfehler 7
0 Error at channel 0
1 Error at channel 1
2 Error at channel 2
3 Error at channel 3
4 ... 7 Reserved 0
Kanalfehler 8 8 ... 15 Reserved 0
Kanalfehler 9 16 ... 23 Reserved 0
Kanalfehler 10 24 ... 31 Reserved 0
Fehler Kanal 0 11
0 Parameter Error
1 Overload
2 Line break sensor supply
3 Fuse blown
4 Line break signal
5 Reserved 0
6 Lower limit exceeded
7 Upper limit exceeded
Diagnosedaten UR20-4AI-UI-16-DIAG
Name Byte Bit Beschreibung Default
Fehler Kanal 1 12
0 Parameter Error
1 Overload
2 Line break sensor supply
3 Fuse blown
4 Line break signal
5 Reserved 0
6 Lower limit exceeded
7 Upper limit exceeded
Fehler Kanal 2 13
0 Parameter Error
1 Overload
2 Line break sensor supply
3 Fuse blown
4 Line break signal
5 Reserved 0
6 Lower limit exceeded
7 Upper limit exceeded
Fehler Kanal 3 14
0 Parameter Error
1 Overload
2 Line break sensor supply
3 Fuse blown
4 Line break signal
5 Reserved 0
6 Lower limit exceeded
7 Upper limit exceeded
Fehler Kanal 4
...
Fehler Kanal 31
15 ... 42 0 ... 7 Reserved 0
Zeitstempel 43-46 time stamp [µs] (32bit)
Prozessdaten
1)
Eingänge UR20-4AI-UI-16-DIAG
Byte Format Beschreibung
IB0
Wort AI0
IB1
IB2
Wort AI1
IB3
IB4
Wort AI2
IB5
IB6
Wort AI3
IB7
1) Internes Prozessdatenmapping bei Datenformat „Standard“. Je nach Feld-
busspezifikation und Datenformateinstellung der kommunizierenden Feldbus-
komponenten können Bytes und/oder Wörter bei der Datenübertragung gedreht
werden.