User manual

6 Detailbeschreibungen I/O-Module | Analoges Eingangsmodul UR20-4AI-UI-16
238 1432780000/08/12.2015Handbuch u-remote
Diagnosedaten UR20-4AI-UI-16
Name Byte Bit Beschreibung Default
Fehlerindikator 0
0 Module error
1 Internal error
2 External error
3 Channel error 0
4 Error
5 Reserved 0
6 Reserved 0
7 Parameter error
Modultyp 1
0
Module Type 0x05
1
2
3
4 Reserved 0
5 Reserved 0
6 Reserved 0
7 Reserved 0
Fehlerbyte 2 2 0 ... 7 Reserved 0
Fehlerbyte 3 3
0 ... 2 Reserved 0
3 Internal diagnostic FIFO full
4 Power supply fault
5 Reserved 0
6 Reserved 0
7 Reserved 0
Kanaltyp 4
0 ... 6 Channel type 0x74
7 Reserved 0
Diagnosenbits
pro Kanal
5
Number of diagnostic bit per
channel
0
Anzahl Kanäle 6
Number of similar channels per
module
4
Kanalfehler 7 ... 10 0 ... 31 Reserved 0
Fehler Kanal 0
...
Fehler Kanal 31
11 ... 42 0 ... 7 Reserved 0
Zeitstempel 43-46 time stamp [µs] (32bit)
Prozessdaten
1)
Eingänge UR20-4AI-UI-16
Byte Format Beschreibung
IB0
Wort AI0
IB1
IB2
Wort AI1
IB3
IB4
Wort AI2
IB5
IB6
Wort AI3
IB7
1) Internes Prozessdatenmapping bei Datenformat „Standard“. Je nach Feld-
busspezifikation und Datenformateinstellung der kommunizierenden Feldbus-
komponenten können Bytes und/oder Wörter bei der Datenübertragung gedreht
werden.