5 Detailed descriptions of the eldbus coupler | DeviceNet eldbus coupler UR20-FBC-DN
97Manual u-remote1432790000/08/12.2015
Object descriptions UR20-FBC-DN: Vendor specific classes
Class Attribute Get Set NV
1)
Data type
2)
Name Description
hex dez
Slot 0x65 (101)
Instance 0x00 (0)
0x64 100 x UINT Revision Revision of this object
0x65 101 x USINT Max Instance Highest possible instance of this object
0x66 102 x USINT Number of Instances Current number of instances
0x67 103 x USINT Max Class Attribute ID of the last attribute of this class in instance0
Instances 0x01 ... 0x40 (1 ... 64)
0x64 100 x x USINT Max Attributes ID of the last instance attribute
0x65 101 x STRING Name Name of the module
0x66 102 x STRING Product Code Order number of the module
0x67 103 x STRING Serial Number Serial number of the module
0x68 104 x UDINT Module ID ID of the module
0x69 105 x STRING Hardware Version Hardware version of the module
0x6A 106 x STRING Software Version Software version of the module
0x6B 107 x STRING MX Version MX version of the module
0x6C 108 x BYTE Slot State
State of the module: 0x01: ok;
0x80: slot empty; 0x81: wrong module; 0x82:
diagnosis active
0x6D 109 x UINT Input Bit Length Length of input data in Bit
0x6E 110 x UINT Output Bit Length Length of output data in Bit
0x6F 111 x UINT Parameter Byte Length Length of parameter data in Byte
0x70 112 x UINT Diag Byte Length Length of diagnosis data in Byte
0x71 113 x Array of BYTE Process Data In Input data of the module
0x72 114 x x Array of BYTE Process Data Out Output data of the module
0x73 115 x x Array of BYTE Parameter Data Parameter data of the module
0x74 116 x Array of BYTE Diagnosis Data Diagnosis data of the module
0x75 117 x Array of BYTE Process Alarm Data Process alarm data of the module
0x76 118 x x Array of BYTE Slot Cong Assembly
Conguration assembly for parameterising the
modules (Rockwell controls)
1) Non volatile (data are saved permanently)
2) For the description of data types refer to table Data types