User manual
5 Detailed descriptions of the eldbus coupler | DeviceNet eldbus coupler UR20-FBC-DN
95Manual u-remote1432790000/08/12.2015
Object descriptions UR20-FBC-DN: CIP Common classes
Class Attribute Get Set NV
1)
Data type
2)
Name Description
hex dez
0x06 6 x BYTE
Initial communication char-
acteristic
Denes the message group(s) associated with this
connection
0x07 7 x UINT Produced connection size Max. number of bytes for this connection
0x08 8 x UINT Consumed connection size Max. number of bytes for this connection
0x09 9 x x UINT Expected packet rate
Time intervall between two messages for this
connection
0x0C 12 x x USINT Watchdog timeout action
Denes how to react on connection activites and
Watchdog timeouts
0x0D 13 x UINT
Produced connection path
length
Number of bytes in the produced connection path
length attribute
0x0E 14 x x Packed EPATH Produced connection path
Species the application object, the data of which
are produced by this connection
0x0F 15 x UINT
Consumed connection path
length
Number of bytes in the consumed connection path
length attribute
0x10 16 x x Packed EPATH Consumed connection path
Species the application object, the data of which
are consumed by this connection
0x11 17 x x UINT Production inhibit time Species the minimum time to produce new data
Acknowledge Handler 0x 2B (43)
Instance 0x00 (0)
0x01 1 x UINT Revision Revision of this object
0x02 2 x UINT Max Instance Maximum number of Instances
Instance 0x01 (1)
0x01 1 x x UINT Acknowledge Timer Time intervall waiting for acknowledgement
0x02 2 x x USINT Retry Limit
Number of Acknowledge Timeouts that must be
achieved before the application gets informed
0x03 3 x x UINT
COS Producing connection
instance
Connection Instance waiting for the acknowledge-
ment of produced data
0x04 4 x BYTE Ack List size
Maximum number of members in the Acknowledge
List
0x05 5 x BYTE and ARRAY of UINT Ack List List of active connections receiving acknowledge
0x06 6 x BYTE Data with Ack Path List Size
Maximum number of data in the acknowledge path
list
0x07 7 x
BYTE and ARRAY of UINT, USINT
and padded EPATH
Data with Ack Path List
List of connection instances and consuming applica-
tion pairs
1) Non volatile (data are saved permanently); 2) For the description of data types refer to table Data types; 3) Reset; 4) Alloc Group2 idset; Release group2 id set;
5)Create; 6) Delete