User manual
5 Detailed descriptions of the eldbus coupler | DeviceNet eldbus coupler UR20-FBC-DN
93Manual u-remote1432790000/08/12.2015
Object descriptions UR20-FBC-DN: CIP Common classes
Class Attribute Get Set NV
1)
Data type
2)
Name Description
hex dez
Identity 0x01 (1)
Instance 0x00 (0)
0x01 1 x UINT Revision Revision of this object
0x02 2 x UINT Max Instance Highest possible instance of this object
Instance 0x01 (1)
3)
0x01 1 x x UINT Vendor ID Vendor ID: 1015
0x02 2 x x UINT DeviceType General type of device: 0x0C
0x03 3 x x UINT Product Code Vendor assigned product code: 33490
0x04 4 x x Struct{USINT,USINT} Revision {Major, Minor} Revision of the u-remote coupler
0x05 5 x WORD Device Status
Bit0: Owned; Bit2= Congured;
Bit4-7:Extended device status;
Bit8: Minor recoverable fault;
Bit9: Minor unrecoverable fault;
Bit10: Major recoverable fault;
Bit 11: Major unrecoverable fault;
Bit12-15: Extended device status 2
0x06 6 x x UDINT Serial Number Serial number of the device; 32 Bit value
0x07 7 x x SHORT_STRING Product Name Product name: UR20-FBC-DN
0x08 8 x USINT State
Status of the device: 0 = Nonexistent, 1 = Device
Self Testing, 2 = Standby, 3 = Operational, 4 =
Major Recoverable Fault, 5 = Major Unrecoverable
Fault, 6 – 254 = Reserved (255 = Default Value)
0x0A 10 x x x USINT Heartbeat Intervall
Periodically sent messages that indicates the
device is still there. The default value is 0 (transmis-
sion of the heartbeat message is disabled).
1) Non volatile (data are saved permanently); 2) For the description of data types refer to table Data types; 3) Reset; 4) Alloc Group2 idset; Release group2 id set;
5)Create; 6) Delete