User manual
5 Detailed descriptions of the eldbus coupler | DeviceNet eldbus coupler UR20-FBC-DN
90 1432790000/08/12.2015Manual u-remote
Overview of editable parameters UR20-FBC-DN
Parameter Optional values Default
Process alarm disabled / enabled disabled
Diagnostic alarm disabled / enabled disabled
Output behaviour on eldbus error All outputs off / Enable substitute value / Hold last value All outputs off
Module behaviour on hot swap Continue data exchange / Behaviour as with eldbus error Continue data exchange
Data format Motorola / Intel Motorola
Save module parameters No / Yes / Standard No
Restore module parameters No / Yes No
Power up baud rate 125kB/s / 250kB/s / 500kB/s / Auto baud / Set by PLC 125kB
Baud rate 125kB/s / 250kB/s / 500kB/s
MAC-ID - Adjustable with rotary switches (values 0 ... 63)
- Adjustable via PLC (Precondition: a value > 63 must be set with the rotary switches)
Assembly Selector Asm 101 & 102 / Asm 103 & 104 Asm 101 & 102
Length of assembly input 2 ... 504
Length of assembly output 2 ... 504
IP-Address USB port 192.168.1.202; 192.168.2.202, 192.168.3.202, 192.168.4.202,
192.168.5.202
192.168.1.202
Major Revision 1 ... 127 Signicant changes concerning form and function
have been realised in a „Major revision“.
Minor Revision 0 ... 255 In a „Minor revision“ changes that do not affect the
user behaviour have been realised.