User manual
5 Detailed descriptions of the eldbus coupler | EtherNet/IP eldbus coupler UR20-FBC-EIP
72 1432790000/08/12.2015Manual u-remote
5.5 EtherNet/IP eldbus coupler UR20-FBC-EIP
The UR20-FBC-EIP eldbus coupler is an EtherNet/IP™ par-
ticipant developed according to IEC 61158. The coupler is
the head module for the u-remote system bus, to which up
to 64 active u-remote modules can be connected. The Eth-
erNet/IP coupler has two Ethernet ports, and the integrated
switch supports a line network structure.
The coupler can be accessed with a system-independent
web server application via the USB service interface or the
Ethernet. Thus all information, such as diagnostics, status
values and parameters, can be read and all connected mod-
ules can be simulated or forced.
The station’s main power supply is integrated in the coupler.
Power is supplied via two 4-pole connectors, separated into
the input and output current paths.
Fieldbus coupler UR20-FBC-EIP (Order No. 1334920000)
Status indicators
PWR
SF
MS*
NS*
EIP
1
2
3
4
1
2
3
4
L/A X1
L/A X2
3
4
X1
X2
LED status indicators UR20-FBC-EIP, error messages seeChapter13
PWR
Power-LED Green: Supply voltage connected
SF
Collective error Red: Conguration error, or error in the coupler,
or error in a module, or there is a new diagnostic
message
Red ashing: Station in Force mode
MS*
Module status Red: More than one module does not t the start-up
conguration
Red ashing: One module does not t the start-up
conguration or there is a diagnosis report on at
least one module
NS*
Network status Off: At least one EtherNet/IP connection is
established
Yellow: Address conict or no IP address cong-
ured
Yellow ashing (1Hz): valid IP address but no
EtherNet/IP connection established
Yellow ashing (4Hz): Connection timeout on an
exclusive owner
L/A X1
Connection/active
Green / Yellow*: Connection established between
port 1 of the coupler and another eld device
Green ashing / Yellow ashing*: Data being
exchanged on port 1
L/A X2
Connection/active
Green / Yellow*: Connection established between
port 2 of the coupler and another eld device
Green ashing / Yellow ashing*: Data being
exchanged on port 2
* Green: Transfer rate 100MBit/s, Yellow: Transfer rate 10MBit/s