70 1432790000/08/12.2015Manual u-remote
0x113C – 0x113F Save module parameters
Load default module parameters (0x113C–0x113D)
loads the default parameter set of all modules (LOAD). This
conforms to the “Standard” option of the parameter “Safe
module parameter” in the web server.
Save module parameters (0x113E–0x113F) stores
the current image of alle module parameters in the coupler
(SAVE). Subsequent changes will not be considered unless
they are saved again. There is no need to enter parameters
again after restarting the coupler. This conforms to the “Yes”
option of the parameter “Safe module parameter” in the web
server.
Input in both register in the Motorola format follow this
scheme
„LOAD“ „SAVE“
Letter of the alphabet L O A D S A V E
ASCII code decimal 076 079 065 068 083 065 086 069
ASCII hexadecimal 4C 4F 41 44 53 41 56 45
Input in register no. 0x113C 0x113D 0x113E 0x113F
Hexadecimal 4C4F 4144 5341 5645
Decimal 19535 16708 21313 22085
Using the Intel format the inputs follow „DAOL“ and „EVAS“:
„DAOL“ „EVAS“
Letter of the alphabet D A O L E V A S
ASCII code decimal 068 065 079 076 069 086 065 083
ASCII hexadecimal 44 41 4F 4C 45 56 41 53
Input in register no. 0x113C 0x113D 0x113E 0x113F
Hexadecimal 4441 4F4C 4556 4153
Decimal 17473 20300 17750 16723
The not editable parameter “Restore module parameters” in
the web server will be set to “Yes” as soon as the coupler
has sent saved parameters to the modules.
0x27FE Number of entries in the current module list
This displays the number of modules that were connected
when the coupler was started.
0x27FF Number of entries in the reference list
This displays the number of modules that were entered into
the reference list.