5 Detailed descriptions of the eldbus coupler | Modbus TCP eldbus coupler UR20-FBC-MOD-TCP
69Manual u-remote1432790000/08/12.2015
0x1130 Writing access in multi-client operation
Bit Name/Description
2 to 15 reserved
1 MB_ImmediateWritePermission
– 0: During the rst write access, write authorisation is requested for the corresponding modbus connection. If this is not successful, an
exception response with the exception code 0x01 is generated. If it is successful, the write access is executed and write authorisation
remains in effect until the end of the connection.
– 1: Write authorisation for the corresponding modbus connection is already requested when the connection is being established. As a re-
sult, the rst modbus connection receives the write authorisation, and nothing happens for all those that follow (as long as Bit 0 = 1).
0 MB_OnlyOneWritePermission
– 0: All modbus connections have write authorisation
– 1: In all cases only one modbus connection can be assigned write authorisation. Once assigned, write authorisation is retained until there
is a disconnect. After the connection that has write authorisation is disconnected, the next connection which attempts write access
receives write authorisation.
0x1131 Modbus connection timeout in sec.
This register determines after which time an inactive modbus
connection will be disconnected.
0x1132 Check reference list prior to data exchange
If the value in this register is set to 0, the data exchange
begins without checking the reference list (0x2800 and the
following) against the current module list (0x2A00 and the
following). The reference list does not need to be created.
If the value in this register is set to 1, the data exchange only
starts if the reference list (0x2800 and the following) match-
es the current module list (0x2A00 and the following). As
long as both lists do not match the eldbus coupler reacts
like on a eldbus error (0x1135).
0x1133 Process alarm
If the value in this register is set to 0, process alarms are re-
ported, but it is not necessary to conrm or read them.
If the value in this register is set to 1, process alarms are
reported and they must be conrmed by reading the corre-
sponding register.
0x1134 Diagnostic alarm
If the value in this register is set to 0, the diagnostic alarm is
deactivated. Pending diagnostics do not have any effect on
the exchange of process data and must not be conrmed.
They are, however, displayed locally on the UR20 hardware
with red LEDs (SF and module) and also can be read in the
module-specic diagnostic registers 0xAXXX.
If the value in this register is set to 1, diagnostics alarms are
reported, and they must be conrmed by reading the corre-
sponding register.
0x1135 Field bus or reference list error behaviour
If the value in this register is set to 0, in case of a eld bus or
reference list error all outputs are set to 0.
If the value in this register is set to 1, in case of a eld bus er-
ror all outputs are set to the substitute values.
If the value in this register is set to 2, in case of a eld bus er-
ror all outputs are held at the last process value.
0x1136 Module removal behaviour
If the value in this register is set to 0, the exchange of pro-
cess data continues.
If the value in this register is set to 1, the behaviour during a
eld bus error is used.
0x1137 Data format
If the value in this register is set to 0, data is transferred in
Motorola format.
If the value in this register is set to 1, data is transferred in
Intel format.