Overview of the editable parameters UR20-FBC-MOD-TCP
Parameter Optional values Default
IP address 4 numbers between 0 and 255 192.168.0.222
Subnet mask 4 numbers between 0 and 255 255.255.255.0
Gateway 4 numbers between 0 and 255 192.168.0.1
IP conguration Static, DHCP, BootP
Firmware 02.00.00 and higher: additionally DHCP and static
Static (rmware 01.xx.xx)
DHCP and static (rmware 02.00.00 or higher)
Modbus DHCP timeout Waiting time, 1 to 1000s 30 s
Additional TCP port
1)
0 (disabled) / Value from 1 to 65535 (except for 80 and 161) 0
IP address USB port
2)
192.168.1.202; 192.168.2.202, 192.168.3.202, 192.168.4.202,
192.168.5.202
192.168.1.202
Web server via Ethernet
2)
disabled / enabled enabled
Save module parameters
1)
no / yes / Standard no, seeregister 0x113C - 0x113F on page70
Status Modbus watchdog Watchdog time in steps of 10ms 0 *10ms, seeregister 0x1120 on page68
Modbus connection timeout Connection watchdog time in sec 1s, seeregister 0x1131 on page69
Writing access in multi-client operation for all connections, for client with rst write access, for client with rst
connection
for all connections, see register 0x1130 on
page69
Check reference list before data exchange disabled / enabled disabled, see register 0x1132 on page69
Process alarm disabled / enabled disabled, seeregister 0x1133 on page69
Diagnostic alarm disabled / enabled disabled, seeregister 0x1134 on page69
Output behaviour on eldbus error All outputs off / Enable substitute value / Hold last value All outputs off, see register 0x1135 on page69
Module behaviour on hot swap Continue data exchange / Behaviour like eldbus error Continue data exchange, see register 0x1136 on
page69
Data format Motorola / Intel Motorola, see register 0x1137 on page69
Lock force mode Force mode unlocked / Force mode locked Force mode unlocked, see register 0x1122 on
page68
1) See description below; 2) Change requires restart of the coupler
Parameter „Additional TCP port“
Another TCP port additionally to the standard port (502) can
be enabled using this parameter. Apart from the values 80
(reserved for http) and 161 (reserved for SNMP) every num-
ber from 1 to 65535 can be used. Value 0 deactivates the
port. The standard port 502 will remain open in any case.
Parameter „Save module parameters“ in the web server
Due to the data structure it is not possible for this parameter
to be set to appear as permanently ‘Yes’ or ‘Standard’. Once
‘Yes’ or ‘Standard’ have been selected, they will still appear
as ‘No’ once the webserver has been closed and re-started.
Option”Standard“: If power is lost to the coupler, any settings
that have been made in the modules will be lost, and default
values loaded once power is restored.
Option “Yes” : Carry out the required module parameter
adjustments, then go into this parameter and change it to
‘Yes’. This must be done every time that module parameters
are changed. Otherwise the changes made to the module
parameters will work until the coupler experiences a loss
of power. Once power is restored, the modules will receive
the settings which were entered the last time the ‘Yes’ com-
mand was carried out
Parameter „Restore module parameters“
This parameter is not editable. It will be automatically set to
“Yes” as soon as the coupler will have sent saved parameter
data to the modules.