User manual

5 Detailed descriptions of the eldbus coupler | Modbus TCP eldbus coupler UR20-FBC-MOD-TCP
58 1432790000/08/12.2015Manual u-remote
Technical data UR20-FBC-MOD-TCP (Order No. 1334930000)
System data
Connection
2 x RJ-45
Fieldbus protocol
Modbus TCP
Multi-client connections
max. 8
Process image
Process data max. 1kBytes
Parameter data max. 1024kBytes
Diagnostic data max. 1024kBytes
Number of modules
max. 64 active
Configuration interface
Micro USB 2.0
Transfer rate
Fieldbus 10Mbps/100Mbps
u-remote system bus max. 48Mbps
Supply
Supply voltage for system and inputs
24VDC +20 % / -15 %
Supply voltage for outputs
24VDC +20 % / -15 %
Max. feed-in current for input modules
10A
Max. feed-in current for output modules
10A
Current consumption from system current path I
SYS
112mA
Connection data
Type of connection
“PUSH IN”
Conductor cross-section
Single-wired, ne-wired 0.14 – 1.5mm
2
(AWG 16 – 26)
Weight
Weight (operational status)
223 g
General data, see Section 3.2
Conguration of the IP address
The web server can be used to dene whether a static IP
address shall be used or the address shall be assigned auto-
matically (DHCP/BootP).
Coupler using rmware version 01.xx.xx are preset to the
static IP address 192.168.0.222.
Coupler using rmware version 02.00.00 or higher will by
default send a DHCP discover rst. If no assigment by a
DHCP server follows during the parameterised waiting time,
the static IP address 192.168.0.222 will be set.