5 Detailed descriptions of the eldbus coupler | Modbus TCP eldbus coupler UR20-FBC-MOD-TCP
55Manual u-remote1432790000/08/12.2015
5.4 Modbus TCP eldbus coupler UR20-FBC-MOD-TCP
The UR20-FBC-MOD-TCP eldbus coupler is a Modbus TCP
participant developed according to IEC 61158. The coupler
is the head module for the u-remote system bus, to which
up to 64 active u-remote modules can be connected. The
Modbus TCP coupler has two Ethernet ports, the integrated
switch supports a line network structure.
The coupler can be accessed with a system-independent
web server application via the USB service interface or the
Ethernet. Thus, all information, such as diagnostics, status
values and parameters, can be read and all connected mod-
ules can be simulated or forced.
The station's main power supply is integrated in the coupler.
Power is supplied via two 4-pole connectors, separated into
the input and output current paths.
Fieldbus coupler UR20-FBC-MOD-TCP (Order No. 1334930000)
Status indicators
PWR
SF
BF
MT
MOD
1
2
3
4
1
2
3
4
L/A X1
L/A X2
3
4
X1
X2
LED status indicators UR20-FBC-MOD-TCP, error messages seeChapter13
PWR
Power LED Green: Supply voltage connected
SF
Collective error Red: Conguration error, or error in the coupler,
or error in a module, or there is a new diagnostic
message
Red ashing: Station in Force mode
BF
Bus failure Red: No connection to the eldbus
Red ashing: Conguration error, no connection
to the control unit, or error in the parameter set
MT
Maintenance Yellow: Error on the system bus or eldbus
L/A X1
Connection/active Green / Yellow
1)
: Connection established between
port 1 of the coupler and another eld device
Green ashing / Yellow ashing
1)
: Data being
exchanged on port 1
L/A X2
Connection/active Green / Yellow
1)
: Connection established between
port 2 of the coupler and another eld device
Green ashing / Yellow ashing
1)
: Data being
exchanged on port 2