13 LEDindicatorsandtroubleshooting | Fieldbus coupler
477Manual u-remote1432790000/08/12.2015
Coupler/indicator LED Status Recommended action
UR20-FBC-CAN
Power LED
PWR Green: Supply voltage
Red: Boot loader failure Have coupler repaired or replaced
Off and the status LED on the module is green: Defective
coupler
Have coupler repaired or replaced
The internal fuse was triggered due to an overload
Off and the status LED on the module is off: Improper supply
voltage
Check the supply voltage
Collective error
SF Red: Conguration error, or error in the coupler, or error in a
module, or there is a new diagnostic message
Redashing: Station in Force mode
Check that the ESI conguration le is up-to-date
Check if the congured station setup matches the actual
setup
Read the diagnostic message with the web server or an
engineering tool and determine which further actions to take
Bus failure
BF Red: No connection to the eldbus Check the eldbus cable and the PLC conguration
Redashing: Conguration error, no connection to the
control unit, or error in the parameter set
Check the eldbus parameters and the PLC conguration
Check that the ESI conguration le is up-to-date
Check if the congured station setup matches the actual
setup
Maintenance
MT Yellow: Error on the system bus or eldbus Check that the modules have been snapped into place
properly
Internal error
ERROR Red: No eldbus communication (BusOFF) Check the eldbus wiring (terminating resistor)
*Redfastashing: Auto baud rate detection running Check the eldbus wiring, restart the eldbus
Redashing: Conguration error Check the conguration, check the bus address
Redoneshortash: CAN error counter reached warning
level
Bad bus physics or collision, check eldbus
Redtwoshortashes: Node guarding (node guard or
heartbeat)
PLC or NMT master failed
Coupler state
RUN Green: Fieldbus running (OPERATIONAL)
Greenashing: Fieldbus in state PRE-OPERATIONAL
*Greenfastashing: Auto baud rate detection running see above
Input supply voltage
3.1 Green: Supply voltage for input current path >18VDC
3.2 Red: Supply voltage for input current path <18VDC Check the supply voltage
3.4 Red: Internal fuse defective Replace the coupler
Output supply voltage
4.1 Green: Supply voltage for output current path >18VDC
4.2 Red: Supply voltage for output current path <18VDC Check the supply voltage
4.4 Red: Internal fuse defective Replace the coupler