User manual
13 LEDindicatorsandtroubleshooting| Fieldbus coupler
476 1432790000/08/12.2015Manual u-remote
Coupler/indicator LED Status Recommended action
UR20-FBC-DN
Power LED
PWR Green: Supply voltage
Red: Boot loader failure Have coupler repaired or replaced
Off and the status LED on the module is green: Defective
coupler
Have coupler repaired or replaced
The internal fuse was triggered due to an overload
Off and the status LED on the module is off: Improper supply
voltage
Check the supply voltage
Collective error
SF Red: Conguration error, or error in the coupler, or error in a
module, or there is a new diagnostic message
Redashing: Station in Force mode
Check that the ESI conguration le is up-to-date
Check if the congured station setup matches the actual
setup
Read the diagnostic message with the web server or an
engineering tool and determine which further actions to take
Bus failure
BF Red: No connection to the eldbus Check the eldbus cable and the PLC conguration
Redashing: Conguration error, no connection to the
control unit, or error in the parameter set
Check the eldbus parameters and the PLC conguration
Check that the ESI conguration le is up-to-date
Check if the congured station setup matches the actual
setup
Maintenance
MT Yellow: Error on the system bus or eldbus Check that the modules have been snapped into place
properly
Module/Network status
MNS Off: Duplicate MAC ID check active
Green: DeviceNet connection established, device status OK
Greenashing: No DeviceNet connection established,
device status OK
Red: Bus failure Check if MAC-ID is duplicated or device is in state BusOFF or
check bus physics
Redashing: Bus connection timeout Check the eldbus for: cable interruption, plug has been
pulled, 24V supply for the eldbus
Input/Output
IO Green: Data exchange active, outputs are accessed by the
PLC
Greenashing: Station in idle mode (outputs are not ac-
cessed by the PLC)
Check if the CPU of the PLC is in STOPP mode
Red: At least one stack differs from the start conguration
(e.g. one module has been pulled)
Check the conguration of the station
Redashing: Diagnostic message on at least one module Read/conrm diagnostic message
Input supply voltage
3.1 Green: Supply voltage for input current path >18VDC
3.2 Red: Supply voltage for input current path <18VDC Check the supply voltage
3.4 Red: Internal fuse defective Replace the coupler
Output supply voltage
4.1 Green: Supply voltage for output current path >18VDC
4.2 Red: Supply voltage for output current path <18VDC Check the supply voltage
4.4 Red: Internal fuse defective Replace the coupler