User manual

Hold the new electronic unit by the top and the bottom,
and carefully slide it into the base module.
The electronic units are functionally coded
so that they can only be inserted into the ap-
propriate base module. If it is not possible to
insert a new electronic unit into the base mod-
ule, check if the combination is correct and if
there is a possible mix-up.
Inserting the new electronic unit
Fold the connector frame back so that it closes and clicks
into place.
In case of replacement during operation: Pay attention to
the collective error LED (SF) on the fieldbus coupler.
Only when this doesn't light up any more, the new elec-
tronic unit has been recognised and the next electronic
unit is able to be pulled out.
11.3 Replacing an I/O module
WARNING
Explosion risk!
Prior to starting work, make sure that
there is not a potentially explosive atmos-
phere!
WARNING
Dangerous contact voltage!
Prior to removing modules, the u-remote
station must be completely de-energised
(supply of the field bus coupler and all
external feed-in).
Make sure that the place of installation
(switch cabinet etc.) has been discon-
nected from the power supply.
ATTENTION
The product can be destroyed by elec-
trostatic discharge!
The components in the u-remote series can
be destroyed by electrostatic discharge.
Please make sure that personnel and work
equipment are adequately earthed!
To remove an individual module from the station, all modules
to the right of it and the termination kit must be moved by
approximately 5cm.
Unfasten the mounting screw on the right-hand end
bracket.
Slide the end bracket and end plate approximately 5cm
to the right or remove both parts from the DIN rail.
Open the release lever on the module furthest to the
right.
11 Replacingcomponents| Replacing an I/O module
464 1432790000/08/12.2015Manual u-remote