User manual

10 Webserver| Updating rmware
458 1432790000/08/12.2015Manual u-remote
Forcing modules with registers (e.g. UR20-1CNT-100-1DO)
Enter the desired value and select the desired register via
the check box
Ending/deactivating forced operations
To cancel a forced operation, click Cancel.
All of the changes you made will not have any effect.
To end a forced operation, close the window.
To deactivate Force mode, click on Deactivate force
mode.
Deactivating force mode
10.11 Updatingrmware
Before you can update the firmware, you must download
the latest firmware file for each coupler and each module
from the Weidmüller website to your local PC.
Firmware les have the extension .bsc (for eldbus couplers)
or .bsm (for modules). For PROFINET couplers, for instance,
the le might be named FBC-PN-IRT-00XX.bsc.
You can determine for each module separately
whether an update shall be proceed.
A rmware update cannot be undone. The old
rmware in the coupler/module is overwritten.
Make sure that the power supply is not in-
terrupted while the rmware les are being
loaded!
To carry out a firmware update, navigate to the web
server and click on Firmware.
The Firmware window opens.
Updating firmware
To select a firmware file, click on Search.
Select the firmware file from the storage location on your
computer and click Open.