User manual
Display after the program starts up
The web server only registers modules that
can communicate on the system bus. Empty
slot modules and other passive modules (e.g.
AUX modules) are not registered by the web
server and thus are not displayed in the screen
view. The numbering of the modules in the
web server view may therefore deviate from
the count in the actual station!
10.4 Activating the Ethernet socket
▶ In the station view, click on the Coupler and then on
Parameters.
▶ Type in the IP address, subnet mask and gateway to be
used.
▶ Make sure that the parameter Web server via Ethernet
is set to enabled.
Activating the Ethernet socket
▶ Enter the required IP address and subnet mask.
▶ Confirm the entry by clicking OK.
▶ Close the coupler window and restart the coupler.
10.5 Setting up registration data and password
protection
If you do not set up a user, all web server functions are ac-
cessible to every user at all times!
As soon as you set up a user with password protection, us-
ers without a user ID will only have read-only rights. Write
access is blocked for them, which means that they cannot
do the following:
– Change parameters
– Operate the station in Force mode
– Load firmware updates
When you start up the web server for the rst time, you are
prompted to enter the registration data. The Change login
data window opens automatically. You can access this win-
dow later via the Coupler status dialogue box (see Section
10.6):
Changing login data, setting up password protection
▶ Enter the user name and password.
▶ To change the login data, enter the new user name and
the new password twice, then click on Change login.
▶ To deactivate password protection, do not enter any new
data, but instead click on No login information.
▶ If you have changed the login data, you must log back in
again afterwards.
10 Webserver | Activating the Ethernet socket
451Manual u-remote1432790000/08/12.2015