User manual
Updating device descriptionles
The naming convention for GSD les (and GSDML les
respectively) always follows this pattern: GSD_V2.3-WI-
UR20-20121214.xml. By reading off the version (V2.3) and
the date (14.12.2012), you can nd out the status of a GSD
le and determine whether you are already using the latest
version.
▶ Download the latest GSD files from the Weidmüller web-
site.
9.3 Commissioning the UR20-FBC-PN-IRT
▶ Start SIMATIC Manager.
▶ To set up a new project, click File/New.
The “New Project” window opens.
▶ Enter a name for the new project (e.g. UR20_Station1)
and click OK.
The new project is displayed in SIMATIC Manager.
Creating a new project
Adding a control unit type
▶ Select the project in SIMATIC Manager.
▶ Select the control unit type VIA Add/Station
(e.g. SIMATIC 300).
Adding a station
▶ Double-click on the project name so that the station
(SIMATIC 300) is displayed below in the directory tree.
▶ Click on the station (SIMATIC 300).
▶ Double-click Hardware on the right-hand side of the
window.
The “Hardware Conguration” window opens.
Hardware configuration
▶ The device catalogue is displayed on the right-hand side
of this window. If this does not occur, open the catalogue
via View/Catalogue.
9 Commissioning| Commissioning the UR20-FBC-PN-IRT
442 1432790000/08/12.2015Manual u-remote