User manual
5 Detailed descriptions of the eldbus coupler | PROFIBUS eldbus coupler UR20-FBC-PB-DP
42 1432790000/08/12.2015Manual u-remote
Technical data UR20-FBC-PB-DP Order No. 1334870000)
System data
Connection
9-pole SUB-D socket
Fieldbus protocol
PROFIBUS DP-V1
Process image
Input data width max. 244 Byte
Output data width max. 244 Byte
Parameter data max. 244 Byte
Diagnostic data max. 244 Byte
Number of modules
max. 64 active
Configuration interface
Micro USB 2.0
Transfer rate
Fieldbus max. 12Mbps
u-remote system bus max. 48Mbps
Supply
Supply voltage for system and inputs
24VDC +20 % / -15 %
Supply voltage for outputs
24VDC +20 % / -15 %
Max. feed-in current for input modules
10A
Max. feed-in current for output modules
10A
Current consumption from system current path I
SYS
100mA
Connection data
Type of connection
“PUSH IN”
Conductor cross-section
Single-wired, ne-wired 0.14 – 1.5mm
2
(AWG 16 – 26)
Weight
Weight (operational status)
223 g
General data, see Section 3.2