User manual
7 Installation
WARNING
Explosion risk!
During assembly work, sparks can form and
surfaces may become excessively hot.
▶ Before assembly, make sure that there is
not a potentially explosive atmosphere!
▶ For applications in potentially explosive
atmospheres, observe the installation and
construction requirements of EN60079-
15 and/or country-specific regulations.
WARNING
Dangerous contact voltage!
▶ Carry out assembly and wiring work on
the u-remote station only when the power
supply is disconnected.
▶ Make sure that the place of installation
(switch cabinet etc.) has been discon-
nected from the power supply!
7.1 Preparations for assembly
The u-remote station is designed for installation in switch
cabinets, terminals or switch boxes in decentralised systems.
The eldbus coupler and I/O modules conform to protection
class IP20.
Environmental conditions
Make sure that the permitted environmental conditions for
installation and operation are observed (see the general tech-
nical data in Sections 3.2 and 3.4).
DIN rail
The u-remote station is designed to be installed on a DINrail
(35 × 7.5mm or 35 x 15mm) made from steel or galvanised
steel according to EN 60715. The DIN rail must be mounted
prior to the installation of the u-remote station.
The DIN rail must be attached to the surface at least every
20cm to protect it from vibration and impact. If it is installed
on earthed mounting plates, it does not have to be sepa-
rately earthed.
Stripping lengths
The required stripping length for every Weidmüller product
is specied in mm. These lengths, e.g. 6mm ±0.5mm,
≥10mm ±1mm, must be observed. This also applies to
the use of wire-end ferrules. The external dimensions of the
crimped wire-end ferrules must conform with IEC-60947-1.
For detailed information see section 7.5.
Unpacking the delivery
All of the elements that make up the u-remote station are
packaged individually for delivery.
▶ Please check the delivery for completeness and transport
damage.
▶ Please report any transport damage immediately to the
respective transport company.
ATTENTION
The product can be destroyed by elec-
trostatic discharge!
The components in the u-remote series can
be destroyed by electrostatic discharge.
▶ Please make sure that personnel and work
equipment are adequately earthed!
▶ Unpack all parts and sort the modules into the installation
sequence as per the instructions.
▶ Dispose of all packaging in accordance with the local dis-
posal guidelines. The cardboard packaging from the mod-
ules and fieldbus couplers can be sent for paper recy-
cling.
7 Installation | Preparations for assembly
419Manual u-remote1432790000/08/12.2015