User manual

6 Detailed descriptions of I/O modules | Power-feed module for output current path UR20-PF-O
404 1432790000/08/12.2015Manual u-remote
Power-feedmoduleforoutputcurrentpathUR20-PF-O(OrderNo.1334740000)
Power-feed modules are used to refresh the current paths
and isolate the power supply. The u-remote station‘s main
power supply is always fed in via the coupler. A power-feed
module UR20-PF-O must be connected if the current de-
mand of the series of output modules is too large.
The maximum feed-in current in the output current path via
the 4-pole connector is 10 A. Details required to calculate
current demand and power supply seesection4.5.
Power-feed modules are passive modules without eldbus
communication, therefore they are not considered during
conguration.
A maximum of three passive modules (power-
feed module, potential distribution module,
empty slot module) may be installed in succes-
sion, however the next module to be installed
must be an active module!
PF-O
4
2
4
3
1
24 V DC
24 V DC
GND
GND
Connection diagram UR20-PF-O
ATTENTION
Risk of material damage!
In the case of a maximum power supply of >8 A and a
maximum temperature of > +55 °C, all four contacts must
be connected with 1.5mm² wiring!
6.55 Power-feed module for output current path UR20-PF-O