User manual
6 Detailed descriptions of I/O modules | Communication module UR20-1COM-SAI-PRO
397Manual u-remote1432790000/08/12.2015
Technical data UR20-1COM-SAI-PRO (Order No. 2007430000)
System data
Data
Process, parameter and diagnostic data depend on the coupler used,
see the table in Section 4.10.
Interface
u-remote system bus
System bus transfer rate
48 Mbps
SAI Interface
Number
1
Type
SAI-PRO Subbus
Transfer rate
250 Bps
Supply voltage
+24 V DC
Current of power supply output
max. 3 A
Short-circuit-proof
yes
Module diagnosis
yes
Individual channel diagnosis
Diagnosis of the subbus modules
Supply
Supply voltage
24 V DC +20 %/-15 %
Current consumption from system current path I
SYS
8mA
Current consumption from input current path I
IN
17mA + SAI supply current
General data
Weight (operational status)
87g
For additional general data see Section 3.4