User manual
6 Detailed descriptions of I/O modules | Digital frequency counter module UR20-2FCNT-100
377Manual u-remote1432790000/08/12.2015
Input filter UR20-2FCNT-100
Limiting frequency Filter time, real value Filter time
187kHz 5,35µs 5µs
94kHz 10,64µs 11µs
47kHz 21,28µs 21µs
23kHz 43,47µs 43µs
12kHz 83,33µs 83µs
6kHz 166,67µs 167µs
3kHz 333,33µs 333µs
1,5kHz 666,67µs 667µs
732Hz 1,36ms 1ms
366Hz 2,73ms 3ms
183Hz 5,46ms 5ms
92Hz 10,87ms 11ms
46Hz 21,74ms 22ms
23Hz 43,47ms 43ms
11Hz 90,90ms 91ms
6Hz 166,67ms 167ms
3Hz 333,33ms 333ms
Diagnostic data UR20-2FCNT-100
Name Bytes Bit Description Default
Error indicator 0
0 Module error
1 Internal error
2 External error
3 Channel error 0
4 Error
5 Reserved 0
6 Reserved 0
7 Parameter error
Module type 1
0
Module Type 0x08
1
2
3
4 Reserved 0
5 Reserved 0
6 Reserved 0
7 Reserved 0
Error byte 2 2 2 ... 7 Reserved 0
Error byte 3 3
0 ... 2 Reserved 0
3 Internal diagnostic FIFO full 0
4 ... 7 Reserved 0
Channel type 4
0 ... 6 Channel type 0x76
7 Reserved 0
Diagnostic bits
per channel
5
Number of diagnostic bit per
channel
0
Number of
channels
6
Number of similar channels per
module
2
Channel error 7 ... 10 0 ... 31 Reserved 0
Channel 0 error
to
Channel 31
error
11
...
42
0 ... 7 Reserved 0
Time stamp 43-46 time stamp [µs] (32bit)