User manual

6 Detailed descriptions of I/O modules | Digital frequency counter module UR20-2FCNT-100
377Manual u-remote1432790000/08/12.2015
Input filter UR20-2FCNT-100
Limiting frequency Filter time, real value Filter time
187kHz 5,35µs 5µs
94kHz 10,64µs 11µs
47kHz 21,28µs 21µs
23kHz 43,47µs 43µs
12kHz 83,33µs 83µs
6kHz 166,67µs 167µs
3kHz 333,33µs 333µs
1,5kHz 666,67µs 667µs
732Hz 1,36ms 1ms
366Hz 2,73ms 3ms
183Hz 5,46ms 5ms
92Hz 10,87ms 11ms
46Hz 21,74ms 22ms
23Hz 43,47ms 43ms
11Hz 90,90ms 91ms
6Hz 166,67ms 167ms
3Hz 333,33ms 333ms
Diagnostic data UR20-2FCNT-100
Name Bytes Bit Description Default
Error indicator 0
0 Module error
1 Internal error
2 External error
3 Channel error 0
4 Error
5 Reserved 0
6 Reserved 0
7 Parameter error
Module type 1
0
Module Type 0x08
1
2
3
4 Reserved 0
5 Reserved 0
6 Reserved 0
7 Reserved 0
Error byte 2 2 2 ... 7 Reserved 0
Error byte 3 3
0 ... 2 Reserved 0
3 Internal diagnostic FIFO full 0
4 ... 7 Reserved 0
Channel type 4
0 ... 6 Channel type 0x76
7 Reserved 0
Diagnostic bits
per channel
5
Number of diagnostic bit per
channel
0
Number of
channels
6
Number of similar channels per
module
2
Channel error 7 ... 10 0 ... 31 Reserved 0
Channel 0 error
to
Channel 31
error
11
 ... 
42
0 ... 7 Reserved 0
Time stamp 43-46 time stamp [µs] (32bit)