User manual

6 Detailed descriptions of I/O modules | Digital counter module UR20-1CNT-500
368 1432790000/08/12.2015Manual u-remote
Process data
1)
outputs UR20-1CNT-500
Byte Format Name Bit Function, when edge 0-1 Remark
QB0  ... QB3 Double word Comparison value -2147483648 (-2
31
) ... +2147483647 (2
31
-1)
QB4 ... QB7 Double word Set value -2147483648 (-2
31
) ... +2147483647 (2
31
-1)
QB8
Word Control word
QX8.0 Activate reset mode
QX8.1 Release comparison bit
QX8.2 Set SW gate
QX8.3 - 8.4 reserved
QX8.5 Load set value loads set value into counter value
QX8.6 Reset status bits Reset of Bits 5.1 to 5.5 of the process data inputs (Compari-
son condition met, End value reached, Overow performed,
Underow performed, Zero-crossing performed)
QX8.7 reserved
QB9
QX9.0 Deactivate reset mode
QX9.1 Disable comparison bit
QX9.2 Reset SW gate
QX9.3 - 9.7 reserved
1) Internal process data mapping with data format “Standard”. Depending on the eldbus specication and the data format of the communicating eldbus compo-
nents the bytes and/or words can be reversed during data transfer.
Process alarm data UR20-1CNT-500
Byte Bit Function
B0
X0.0 - 0.1 reserved
X0.2 Overow, underow or end value reached
X0.3 Comparison value reached
X0.4 - 0.7 reserved
B1
X1.0 Status Input channel 0 A (track A)
X1.1 Status Input channel 0 B (track B)
X1.2 Status Input Reset
X1.3 - 1.7 reserved
B2
16 Bit Time stamp 0 ... 65535µs, rotating
B3