User manual

6 Detailed descriptions of I/O modules | Digital counter module UR20-1CNT-500
366 1432790000/08/12.2015Manual u-remote
Diagnostic data UR20-1CNT-500
Name Bytes Bit Description Default
Error indicator 0
0 Module error
1 Internal error
2 External error
3 Channel error
4 External auxiliary supply error
5 Reserved 0
6 Reserved 0
7 Parameter error
Module type 1
0
Module Type 0x08
1
2
3
4 Reserved 1
5 Reserved 0
6 Reserved 0
7 Reserved 0
Error byte 2 2 0 – 7 Reserved 0
Error byte 3 3
0 – 2 Reserved 0
3 Internal diagnostic FIFO full
4 Reserved 0
5 Process alarm lost 0
6 Reserved 0
7 Reserved 0
Channel type 4
0 – 6 Channel type 0x76
7 Reserved 0
Diagnostic bits
per channel
5
Number of diagnostic bit per
channel
8
Number of
channels
6
Number of similar channels per
module
1
Channel error 7
0 Error at channel 0
1 – 7 Reserved 0
Channel error 8 8 – 15 Reserved 0
Channel error 9 16 – 23 Reserved 0
Channel error 10 24 – 31 Reserved 0
Channel 0 error 11
0 – 1 Reserved 0
2 Overow/underow/end value
3 Comparison value reached
4 – 7 Reserved 0
Channel 1 error
to
Channel 31
error
12 – 42 0 – 7 Reserved 0
Time stamp 43 – 46 Time stamp [µs] (32bit)