User manual
6 Detailed descriptions of I/O modules | Digital counter module UR20-1CNT-500
364 1432790000/08/12.2015Manual u-remote
Technical data UR20-1CNT-500 (Order No. 1315580000)
System data
Data
Process, parameter and diagnostic data depend on the coupler used,
see the table in Section 4.10.
Interface
u-remote system bus
System bus transfer rate
48 Mbps
Digital inputs
Number of counter inputs
1
Input type
RS422, suitable for diffential rotary encoders
Input filter
Filter time adjustable from 1.3 µs to 1ms
Maximum input voltage
25VDC
Dielectric strength
up to 30VDC max.
Sensor supply
500 mA max. (feed-in 24 V); 400 mA max. (feed-in 5 V)
Short-circuit-proof
yes
Reverse polarity protection
yes
Module diagnosis
yes
Individual channel diagnosis
no
Counter width
32 bits
Maximum input frequency
500kHz
Mode of operation
Pulse and direction / AB mode with 1-, 2-, 4-times sampling
Status, alarm, diagnostics
Status indicator
yes
Process alarm
yes, parameterisable
Diagnostic alarm
yes
Supply
Supply voltage
24V DC +20 %/-15 %
Current consumption from system current path I
SYS
8mA
Current consumption from input current path I
IN
20mA
General data
Weight (operational status)
72 g