6 Detailed descriptions of I/O modules | Digital counter module UR20-2CNT-100
358 1432790000/08/12.2015Manual u-remote
Counting range
Limits Valid range of values
End value –2 147 483 647 (–2
31
+1) to +2 147 483 647 (2
31
 –1)
Lower count limit +2 147 483 648 (-2
31
)
Periodic counting / primary direction down
Upper
count limit
Load value
End value
0
Gate start Gate stop
Counting value
Time
Periodic counting, primary direction down.
Down-counting starts at the load value.
If the parameterised end value +1 is reached during
counting in the negative direction, the counter jumps
back to the load value at the next count pulse and contin-
ues counting from there. The status bit "End value rea-
ched" is set and a process alarm will be triggered if it is
parameterised.
Upon reaching the upper count limit the counter jumps to
the lower count limit to continue counting from there.
The status bit "Overflow performed" is set and a process
alarm will be triggered if it is parameterised. All status
bits remain set until they are reset with the bit "Reset sta-
tus bits" in the control word.
Counting range
Limits Valid range of values
End value –2 147 483 647 (–2
31
) to +2 147 483 646 (2
31
 –2)
Upper count limit +2 147 483 647 (2
31 
–1)
Additional counter features
You can dene the additional features for the counter listed
below by parametrising or via the process data outputs:
Reset: resets the counting value to the load value during
counting.
Comparator: Upon meeting the comparison condition,
the comparison bit is activated or a process alarm is trig-
gered.
Hysteresis: reduces frequent toggling of the comparison
bit and/or excessive triggering of a process alarm, e.g.
when the value of a sensor signal fluctuates around the
comparison value.
Comparison value Process alarm
Comparator
Hysteresis
Counting value
Load value
Internal gate
SW gate Pulse/track A
Pulse evaluation
Direction/track B Reset
Release
Additional counter functions.