6 Detailed descriptions of I/O modules | Digital counter module UR20-2CNT-100
354 1432790000/08/12.2015Manual u-remote
Process data
1)
outputs UR20-2CNT-100
Byte Format Name Bit Function, when edge 0-1 Remark
QB0  ... QB3 Double word
Counter 0:
Comparison value
QB4 ... QB7 Double word
Counter 1:
Comparison value
QB8
Word
Counter 0:
Control word
QX8.0 reserved
QX8.1 Release comparison bit
QX8.2 Set SW gate
QX8.3 - 8.4 reserved
QX8.5 Load set value loads set value into counter value
QX8.6 Reset status bits Counter 0: status bits 9.1 - 9.5
QB9
QX8.7 - 9.0 reserved
QX9.1 Deactivate comparison bit
QX9.2 Reset SW gate
QX9.3 - 9.7 reserved
QB10
Word
Counter 1:
Control word
QX10.0 reserved
QX10.1 Release comparison bit
QX10.2 Set SW gate
QX10.3 - 10.4 reserved
QX10.5 Load set value loads set value into counter value
QX10.6 Reset status bits Counter 1: status bits 11.1 - 11.5
QB11
QX10.7 - 11.0 reserved
QX11.1 Deactivate comparison bit
QX11.2 Reset SW gate
QX11.3 - 11.7 reserved
1) Internal process data mapping with data format “Standard”. Depending on the eldbus specication and the data format of the communicating eldbus compo-
nents the bytes and/or words can be reversed during data transfer.
Process alarm data UR20-2CNT-100
Byte Bit Function
B0
X0.0 - 0.1 reserved
X0.2 Counter 0: Overow, underow or end value reached
X0.3 Counter 0: Comparison value reached
X0.4 - 0.5 reserved
X0.6 Counter 1: Overow, underow or end value reached
X0.7 Counter 1: Comparison value reached
B1
X1.0 Status Counter 0: Input channel 0 A (track A)
X1.1 Status Counter 0: Input channel 0 B (track B)
X1.2 Status Counter 1: Input channel 0 A (track A)
X1.3 Status Counter 1: Input channel 0 B (track B)
X1.4 - 1.7 reserved
B2
16 Bit Time stamp 0 ... 65535µs, rotating
B3