6 Detailed descriptions of I/O modules | Digital counter module UR20-2CNT-100
351Manual u-remote1432790000/08/12.2015
Overview of the editable parameter UR20-2CNT-100
Channel Description Options
1)
Default
Diagnostic alarm disabled (0) / enabled (1) disabled
0 ... 1 Filter time signal A
0.010 ms [100kHz] (0) / 0.020 ms [50kHz] (1) / 0.033 ms [30kHz] (2) /
0.1 ms [10kHz] (3) / 0.2 ms [5kHz] (4) / 0.5 ms [2kHz] (5) / 1 ms [1kHz] (6)
0.010 ms [100kHz]
0 ... 1 Filter time signal B
0 ... 1 Process alarm overow disabled (0) / enabled (1) disabled
0 ... 1 Process alarm underow disabled (0) / enabled (1) disabled
0 ... 1 Process alarm comp. value disabled (0) / enabled (1) disabled
0 ... 1 Process alarm end value disabled (0) / enabled (1) disabled
0 ... 1 Counting mode count endless (0) / once - forward (1) / once - backwards (2) /
once - no main direction (3) / periodic - forward (4) /
periodic - backwards (5) / periodic - no main direction (6)
count endless
0 ... 1 Comparison function disabled (0) / higher equal comparison value (1) / lower equal comparison value (2)/
equal comparison value (3)
disabled
0 ... 1 Counter dir. signal B inv. disabled (0) / enabled (1) disabled
0 ... 1 Signal mode Rotary transducer - single (0) / Rotary transducer - double (1) / Rotary transducer -
quadruple (2) / Pulse and Direction (3) / Counter disabled (4)
Counter disabled
0 ... 1 Counter behaviour internal gate Interrupt counting (0) / Cancel counting (1) Cancel counting
0 ... 1 Setting value -2147483648 ... 2147483647 0
0 ... 1 End value -2147483648 ... 2147483647 2147483647
0 ... 1 Load value -2147483648 ... 2147483647 0
0 ... 1 Hysteresis 0 ... 255 0
1) Values in brackets for Modbus-TCP (firmware version 02.00.00 and higher) and EtherCAT
The parameter setting in the coupler for the
Output behaviour on eldbus error affects
the control word and thus the behaviour of the
UR20-2CNT-100:
– The Hold last value setting
The counter continues to count during the error. Once
normal operating conditions have been restored, the
counter continues to count starting at the previous value.
– The Enable substitute value setting
The counter value is frozen. Once normal operating condi-
tions have been restored, the counter value is reset to the
parameterised load value.
– All outputs off setting
The counter behaves in the same way as for Hold last
value.