Periodic counting / no primary direction
Upper
count limit
Lower
count limit
Load value
Zero
crossing
Overrun
Underrun
Gate start Gate stop
Counting value
0
Time
Periodic counting, no primary counting direction
Counting (up or down) starts at the load value, the entire
counting range is used.
Upon reaching a count limit, the counter jumps to the
load value and starts counting again from there. The sta-
tus bit "Overflow performed" or "Underflow performed" is
set and a process alarm will be triggered if it is parame-
terised. All status bits remain set until they are reset with
the bit "Reset status bits" in the control word.
Periodic counting / primary direction up
Upper
count limit
Lower
count limit
Load value
Overrun
Underrun
Gate start Gate stop
Counting value
0
Time
Periodic counting, primary counting direction up.
Up-counting starts at the load value.
If the parametrerised end value -1 is reached during
counting in the positive direction, the counter jumps back
to the load value at the next positive count pulse and con-
tinues counting from there. The status bit "End value
reached" is set and a process alarm will be triggered if it
is parameterised.
Upon reaching the lower count limit the counter jumps to
the upper count limit to continue counting from there.
The status bit "Underflow performed" is set and a process
alarm will be triggered if it is parameterised. All status
bits remain set until they are reset with the bit "Reset sta-
tus bits" in the control word.
Counting range
Limits Valid range of values
End value –2 147 483 647 (–2
31
+1) to +2 147 483 647 (2
31
 –1)
Lower count limit +2 147 483 648 (-2
31
)
Periodic counting / primary direction down
Upper
count limit
Load value
End value
0
Gate start Gate stop
Counting value
Time
Periodic counting, primary counting direction down.
Down-counting starts at the load value.
If the parametrerised end value +1 is reached during
counting in the negative direction, the counter jumps
back to the load value at the next count pulse and contin-
ues counting from there. The status bit "Endvalue
reached" is set and a process alarm will be triggered if it
is parameterised.
Upon reaching the upper count limit the counter jumps to
the lower count limit to continue counting from there.
The status bit "Overflow performed" is set and a process
alarm will be triggered if it is parameterised. All status
bits remain set until they are reset with the bit "Reset sta-
tus bits" in the control word.
Counting range
Limits Valid range of values
End value –2 147 483 647 (–2
31
) to +2 147 483 646 (2
31
 –2)
Upper count limit +2 147 483 647 (2
31 
–1)