User manual

6 Detailed descriptions of I/O modules | Digital counter module UR20-1CNT-100-1DO
339Manual u-remote1432790000/08/12.2015
Process data
1)
outputs UR20-1CNT-100-1DO
Byte Format Name Bit Function, when edge 0-1 Remark
QB0 ...QB3 Double word Comparison value
depending on parametrization for triggering of process alarm
or setting the DO, as soon as the condition is met
QB4 ... QB7 Double word Set value
this value is copied into counter value in the event of edge
0-1 at bit 5 of the control word
QB8
Word Control word
QX8.0 Activate reset mode
QX8.1 Release DO
QX8.2 Set SW gate
QX8.3 - 8.4 reserved
QX8.5 Load set value loads set value into counter value
QX8.6 Reset status bits counter status bits 9.1 - 9.5
QX8.7 reserved
QX9.0 Deactivate reset mode
QB9
QX9.1 Block DO
QX9.2 Reset SW gate
QX9.3 - 9.7 reserved
1) Internal process data mapping with data format “Standard”. Depending on the eldbus specication and the data format of the communicating eldbus compo-
nents the bytes and/or words can be reversed during data transfer.
Process alarm data UR20-1CNT-100-1DO
Byte Bit Function
B0
X0.0 HW gate activated
X0.1 HW gate deactivated
X0.2 Overow, underow or end value reached
X0.3 Comparison value reached
X0.4 Latch value reached
X0.5 - 0.7 reserved
B1
X1.0 Status input channel 0 A (track A)
X1.1 Status input channel 0 B (track B)
X1.2 Status input "Latch"
X1.3 Status input "Gate"
X1.4 Status input "Reset"
X1.5 - 1.7 reserved
B2
16 bit time stamp 0 ... 65535µs, rotating
B3