User manual

6 Detailed descriptions of I/O modules | Digital counter module UR20-1CNT-100-1DO
337Manual u-remote1432790000/08/12.2015
The parameter setting in the coupler for the
Output behaviour on eldbus error affects
the control word and thus the behaviour of the
UR20-1CNT-100-1DO:
The Hold last value setting
The output continues working or switches as prametrized
respectively.
The counter continues to count during the error. Once
normal operating conditions have been restored, the
counter continues to count starting at the previous value.
The Enable substitute value setting
The output is switched off.
The counter value is frozen. Once normal operating condi-
tions have been restored, the counter value is reset to the
parameterised load value.
All outputs off setting
The output is switched off.
The counter behaves in the same way as for Hold last
value.
Diagnostic data UR20-1CNT-100-1DO
Name Bytes Bit Description Default
Error indicator 0
0 Module error
1 Internal error
2 External error
3 Channel error
4 External auxiliary supply error
5 Reserved 0
6 Reserved 0
7 Parameter error
Module type 1
0
Module Type 0x08
1
2
3
4 Channel information available 1
5 Reserved 0
6 Reserved 0
7 Reserved 0
Error byte 2 2 0 – 7 Reserved 0
Error byte 3 3
0 – 2 Reserved 0
3 Internal diagnostic FIFO full
4 Reserved 0
5 Reserved 0
6 Process alarm lost
7 Reserved 0
Channel type 4
0 – 6 Channel type 0x76
7 Reserved 0
Diagnostic bits
per channel
5
Number of diagnostic bit per
channel
8
Number of
channels
6
Number of similar channels per
module
1
Channel error 7
0 Error at channel 0
1 – 7 Reserved 0
Channel error 8 8 – 15 Reserved 0
Channel error 9 16 – 23 Reserved 0
Channel error 10 24 – 31 Reserved 0
Channel 0 error 11
0 Hardware gate opened
1 Hardware gate closed
2 Overow/underow/end value
3 Comparison value reached
4 Latch value saved
5 – 7 Reserved 0
Channel 1 error
to
Channel 31
error
12
to
42
0 – 7 Reserved 0
Time stamp 43 – 46 Time stamp [µs] (32bit)