User manual
6 Detailed descriptions of I/O modules | Digital counter module UR20-1CNT-100-1DO
336 1432790000/08/12.2015Manual u-remote
Technical data UR20-1CNT-100-1DO (Order No. 1315570000)
General data
Weight (operational status)
83 g
For additional general data, see Section 3.4
Overview of the editable parameter UR20-1CNT-100-1DO
Channel Description Options
1)
Default
Diagnostic alarm disabled (0) / enabled (1) disabled
0 Filter time signal A
0.010 ms [100kHz] (0) / 0.020 ms [50kHz] (1) / 0.033 ms [30kHz] (2) /
0.1 ms [10kHz] (3) / 0.2 ms [5kHz] (4) / 0.5 ms [2kHz] (5) / 1 ms [1kHz] (6)
0,010 ms [100kHz]
0 Filter time signal B
0 Filter time latch
0 Filter time gate
0 Filter time reset
0 Process alarm HW gate open disabled (0) / enabled (1) disabled
0 Process alarm HW gate closed disabled (0) / enabled (1) disabled
0 Process alarm overow disabled (0) / enabled (1) disabled
0 Process alarm underow disabled (0) / enabled (1) disabled
0 Process alarm comp. value disabled (0) / enabled (1) disabled
0 Process alarm end value disabled (0) / enabled (1) disabled
0 Process alarm latch value disabled (0) / enabled (1) disabled
0 Counting mode count endless (0) / once - forward (1) / once - backwards (2) / once - no main direction (3) / periodic -
forward (4) / periodic - backwards (5) / periodic - no main direction (6)
count endless
0 Condition for DO disabled (0) / higher equal comparison value (1) / lower equal comparison value (2)/ equal comparison
value (3)
disabled
0 Counter dir. signal B inv. disabled (0) / enabled (1) disabled
0 Reset disabled (0) / high level (1) / rising edge 0-1 (2)/ rising edge once 0-1 (3) disabled
0 Signal mode Rotary transducer - single (0) / Rotary transducer - double (1) / Rotary transducer - quadruple (2) / Pulse
and Direction (3) / Counter disabled (4)
Counter disabled
0 HW gate disabled (0) / enabled (1) disabled
0 Counter behaviour internal gate Interrupt counting (0) / Cancel counting (1) Cancel counting
0 End value -2147483648 ... 2147483647 2147483647
0 Load value -2147483648 ... 2147483647 0
0 Hysteresis 0 ... 255 0
0 Pulse duration 0 ... 255 [Input value x 2 = output time in ms; corresponds to 0 ... 510ms] 0
1) Values in brackets for Modbus-TCP (firmware version 02.00.00 and higher) and EtherCAT