User manual
6 Detailed descriptions of I/O modules | Digital counter module UR20-1CNT-100-1DO
335Manual u-remote1432790000/08/12.2015
Technical data UR20-1CNT-100-1DO (Order No. 1315570000)
System data
Data
Process, parameter and diagnostic data depend on the coupler used,
see the table in Section 4.10.
Interface
u-remote system bus
System bus transfer rate
48 Mbps
Digital inputs
Number of counter inputs
1
Input type
Input characteristics for sensor types 1 and 3 are in accordance with EN61131-2, suitable for
incremental encoders and others
Input filter
Filter time adjustable from 0.01 to 1ms
Low input voltage
< 5V
High input voltage
> 11V
Max. input current per channel
3.5mA
Sensor supply
yes
Sensor connection
2-wire, 3-wire
Reverse polarity protection
yes
Module diagnosis
yes
Individual channel diagnosis
yes
Counter width
32 bits
Maximum input frequency
100kHz
Latch, gate, reset input
yes
Mode of operation
Pulse and direction / AB mode with 1-, 2-, 4-times sampling
Status, alarm, diagnostics
Status indicator
yes
Process alarm
yes, parameterisable
Diagnostic alarm
yes
Outputs
Number
1
Output current
0.5A
Reverse polarity protection
yes
Module diagnosis
yes
Individual channel diagnosis
yes
Supply
Supply voltage
24V DC +20 %/-15 %
Current consumption from system current path I
SYS
8mA
Current consumption from input current path I
IN
35mA (plus output current for the digital output)