6 Detailed descriptions of I/O modules | Analogue output module UR20-4AO-UI-16-DIAG-HD
329Manual u-remote1432790000/08/12.2015
Diagnostic data UR20-4AO-UI-16-DIAG-HD
Name Byte Bit Description Default
Error indicator 0
0 Module error
1 Internal error
2 External error
3 Channel error
4 Reserved 0
5 Power supply fault
6 Reserved 0
7 Parameter error
Module type 1
0
Module Type 0x05
1
2
3
4 Channel information available 1
5 ... 7 Reserved 0
Error byte 2 2 0 ... 7 Reserved 0
Error byte 3 3
0 ... 2 Reserved 0
3 Internal diagnostic FIFO full
4 Power supply fault
5 Reserved 0
6 Reserved 0
7 Reserved 0
Channel type 4
0 ... 6 Channel type 0x73
7 Reserved 0
Diagnostic bits
per channel
5
Number of diagnostic bit per
channel
8
Number of
channels
6
Number of similar channels per
module
4
Channel error
7
0 Error at channel 0
1 Error at channel 1
2 Error at channel 2
3 Error at channel 3
4 ... 7 Reserved 0
8 ... 10 0 ... 31 Reserved 0
Channel 0 error 11
0 Parameter Error
1 Overtemperature
2 Overload
3 Error
4 Line break
5 ... 7 Reserved 0
Channel 1 error 12
0 Parameter Error
1 Overtemperature
2 Overload
3 Error
4 Line break
5 ... 7 Reserved 0
Diagnostic data UR20-4AO-UI-16-DIAG-HD
Name Byte Bit Description Default
Channel 2 error 13
0 Parameter Error
1 Overtemperature
2 Overload
3 Error
4 Line break
5 ... 7 Reserved 0
Channel 3 error 14
0 Parameter Error
1 Overtemperature
2 Overload
3 Error
4 Line break
5 ... 7 Reserved 0
Channel 4
error...
Channel 31
error
15 ... 42 0 ... 7 Reserved 0
Time stamp 43 ... 46 time stamp [µs] (32bit)