User manual

6 Detailed descriptions of I/O modules | Analogue output module UR20-4AO-UI-16-DIAG
314 1432790000/08/12.2015Manual u-remote
Diagnostic data UR20-4AO-UI-16-DIAG
Name Bytes Bit Description Default
Error indicator 0
0 Module error
1 Internal error
2 External error
3 Channel error
4 Reserved 0
5 Power supply fault
6 Reserved 0
7 Parameter error
Module type 1
0
Module Type 0x05
1
2
3
4 Channel information available 1
5 – 7 Reserved 0
Error byte 2 2 0 – 7 Reserved 0
Error byte 3 3
0 – 2 Reserved 0
3 Internal diagnostic FIFO full
4 Power supply fault
5 Reserved 0
6 Process alarm lost
7 Reserved 0
Channel type 4
0 – 6 Channel type 0x73
7 Reserved 0
Diagnostic bits
per channel
5
Number of diagnostic bit per
channel
8
Number of
channels
6
Number of similar channels
per module
4
Channel error
7
0 Error at channel 0
1 Error at channel 1
2 Error at channel 2
3 Error at channel 3
4 ... 7 Reserved 0
8 ... 10 0 ... 31 Reserved 0
Error Channel 0 11
0 Parameter Error
1 Overtemperature
2 Overload
3 Error
4 Line break
5 ... 7 Reserved 0
Error Channel 1 12
0 Parameter Error
1 Overtemperature
2 Overload
3 Error
4 Line break
5 ... 7 Reserved 0
Diagnostic data UR20-4AO-UI-16-DIAG
Name Bytes Bit Description Default
Error Channel 2 13
0 Parameter Error
1 Overtemperature
2 Overload
3 Error
4 Line break
5 ... 7 Reserved 0
Error Channel 3 14
0 Parameter Error
1 Overtemperature
2 Overload
3 Error
4 Line break
5 ... 7 Reserved 0
Channel 4 error
to Channel 31
error
15 – 42 0 – 7 Reserved 0
Time stamp 43 – 46 Time stamp [µs] (32bit)
Process data
1)
outputs UR20-4AO-UI-16-DIAG
Byte Format Description
QB0
Word AO0
QB1
QB2
Word AO1
QB3
QB4
Word AO2
QB5
QB6
Word AIO3
QB7
1) Internal process data mapping with data format “Standard”. Depending on
the eldbus specication and the data format of the communicating eldbus
components the bytes and/or words can be reversed during data transfer.