User manual
6 Detailed descriptions of I/O modules | Analogue output module UR20-4AO-UI-16
309Manual u-remote1432790000/08/12.2015
Output range
1
UR20-4AO-UI-16
Output range Current (I) /
Voltage (U)
Decimal (D) Hexadecimal Range Conversion
0 … 5V
Siemens S5 format
5,88V 19268 0x4B44 Overloading
D= 16384 x U / 5
U=D x 5 / 16384
5V 16384 0x4000
Nominal range2,5V 8192 0x2000
0V 0 0x0000
±5 V
Siemens S7 format
5,88V 32511 0x7EFF Overloading
D= 27648 x U / 5
U=D x 5 / 27648
5V 27648 0x6C00
Nominal range
2,5 13824 0x3600
0 V 0 0x0000
-2,5 V -13824 0xCA00
-5V -27648 0x9400
-5,88V -32511 0x8100 Underloading
±5 V
Siemens S5 format
5,88V 19268 0x4B44 Overloading
D= 16384 x U / 5
U=D x 5 / 16384
5V 16384 0x4000
Nominal range
2,5 8192 0x2000
0 V 0 0x0000
-2,5 V -8192 0xE000
-5V -16384 0xC000
-5,88V -19268 0xB4BC Underloading
1) If the process value is beyond the valid output range, the corresponding channel releases 0V and 0mA respectively.
The following applies for all S5 and S7 ranges:
value > overload range = output deactivated
value < underload range = output deactivated