User manual
6 Detailed descriptions of I/O modules | Analogue input module UR20-4AI-RTD-DIAG
292 1432790000/08/12.2015Manual u-remote
Resistance measurement ranges UR20-4AI-RTD-DIAG
Measurement range Resistance Decimal Hexadecimal Range
40Ω
> 47.04Ω 32767 0x7FFF Overloading or line break
47.04Ω 32511 0x7EFF Overloading
40Ω 27648 0x6C00 Nominal range
0 0 0x0000
80Ω
> 94.07Ω 32767 0x7FFF Overloading or line break
94.07Ω 32511 0x7EFF Overloading
80Ω 27648 0x6C00 Nominal range
0 0 0x0000
150Ω
> 176.4Ω 32767 0x7FFF Overloading or line break
176.4Ω 32511 0x7EFF Overloading
150Ω 27648 0x6C00 Nominal range
0 0 0x0000
300Ω
> 352.77Ω 32767 0x7FFF Overloading or line break
352.77Ω 32511 0x7EFF Overloading
300Ω 27648 0x6C00 Nominal range
0 0 0x0000
500Ω
> 587.9Ω 32767 0x7FFF Overloading or line break
587.9Ω 32511 0x7EFF Overloading
500Ω 27648 0x6C00 Nominal range
0 0 0x0000
1kΩ
> 1.177kΩ 32767 0x7FFF Overloading or line break
1.177kΩ 32511 0x7EFF Overloading
1.0kΩ 27648 0x6C00 Nominal range
0 0 0x0000
2kΩ
2.352kΩ 32767 0x7FFF Overloading or line break
2.352kΩ 32511 0x7EFF Overloading
2.0kΩ 27648 0x6C00 Nominal range
0 0 0x0000
4kΩ
> 4.703kΩ 32767 0x7FFF Overloading or line break
4.703kΩ 32511 0x7EFF Overloading
4.0kΩ 27648 0x6C00 Nominal range
0 0 0x0000