User manual
6 Detailed descriptions of I/O modules | Analogue input module UR20-8AI-I-16-DIAG-HD
279Manual u-remote1432790000/08/12.2015
Overview of the editable parameters UR20-8AI-I-16-DIAG-HD
Channel Description Options
1)
Default
Frequency suppression disabled (0) / 50Hz (1) / 60Hz (2) / Average over 16 values (3) disabled
0 ... 7 Channel diagnostics disabled (0) / enabled (1) disabled
0 ... 7 Diag short circuit 24V disabled (0) / enabled (1) disabled
0 ... 7 Data format S5 Data format (0) / S7 Data format (1) S7 Data format
0 ... 7 Measurement range
0
to 20 mA (0) / 4 to 20 mA (1) / disabled (2)
disabled
1) Values in brackets for Modbus-TCP (firmware version 02.00.00 and higher) and EtherCAT
Process data
1)
inputs UR20-8AI-I-16-DIAG-HD
Byte Format Description
IB0
Word AI0
IB1
IB2
Word AI1
IB3
IB4
Word AI2
IB5
IB6
Word AI3
IB7
IB8
Word AI4
IB9
IB10
Word AI5
IB11
IB12
Word AI6
IB13
IB14
Word AI7
IB15
1) Internal process data mapping with data format “Standard”. Depending on
the eldbus specication and the data format of the communicating eldbus
components the bytes and/or words can be reversed during data transfer.