User manual

6 Detailed descriptions of I/O modules | Analogue input module UR20-4AI-UI-16-DIAG-HD
257Manual u-remote1432790000/08/12.2015
AnalogueinputmoduleUR20-4AI-UI-16-DIAG-HD(OrderNo.1506910000)
The UR20-4AI-UI-16-DIAG-HD analogue input module can
record up to 4analogue sensors with ±10V, ±5V, 0 ... 10V,
0 ... 5V, 2 ... 10V, 1 ... 5V, 0 ... 20mA or 4 ... 20mA. The reso-
lution is 16bit per channel. Sensors can be connected to
each connector in a 2-wire, 3-wire or 3-wire connection + FE
(IDC). The measurement range is dened using parameteri-
sation. A status LED is assigned to each channel. The mod-
ule electronics supply the connected sensors with power
from the input current path (I
IN
).
Each sensor output is loadable with 500mA and protected
agains overcurrent. The inputs are protected against voltage
surges and overcurrent. Voltages that exceed ±30V may
cause the destruction of the module. As a protection against
overcurrent, the module temporarily switches to voltage
mode.
The module provides individual channel diagnosis with chan-
nel related error messages.
4AUI·16·D
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
4AUI·16·D
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
AI 0
GND
24 V DC
FE
AI 1
GND
24 V DC
FE
AI 2
GND
24 V DC
FE
AI 3
GND
24 V DC
FE
AI 0
GND
24 V DC
FE
AI 1
GND
24 V DC
FE
AI 2
GND
24 V DC
FE
AI 3
GND
24 V DC
FE
Connection diagram UR20-4AI-UI-16-DIAG-HD (left 3/4-wire sensor with sensor wiring via electron-
ics, right: 2-wire sensor with sensor wiring via electronics)
6.34 Analogue input module UR20-4AI-UI-16-DIAG-HD