User manual
6 Detailed descriptions of I/O modules | Analogue input module UR20-4AI-UI-16-DIAG-HD
257Manual u-remote1432790000/08/12.2015
AnalogueinputmoduleUR20-4AI-UI-16-DIAG-HD(OrderNo.1506910000)
The UR20-4AI-UI-16-DIAG-HD analogue input module can
record up to 4analogue sensors with ±10V, ±5V, 0 ... 10V,
0 ... 5V, 2 ... 10V, 1 ... 5V, 0 ... 20mA or 4 ... 20mA. The reso-
lution is 16bit per channel. Sensors can be connected to
each connector in a 2-wire, 3-wire or 3-wire connection + FE
(IDC). The measurement range is dened using parameteri-
sation. A status LED is assigned to each channel. The mod-
ule electronics supply the connected sensors with power
from the input current path (I
IN
).
Each sensor output is loadable with 500mA and protected
agains overcurrent. The inputs are protected against voltage
surges and overcurrent. Voltages that exceed ±30V may
cause the destruction of the module. As a protection against
overcurrent, the module temporarily switches to voltage
mode.
The module provides individual channel diagnosis with chan-
nel related error messages.
4AI·UI·16·D
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
4AI·UI·16·D
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
AI 0
GND
24 V DC
FE
AI 1
GND
24 V DC
FE
AI 2
GND
24 V DC
FE
AI 3
GND
24 V DC
FE
AI 0
GND
24 V DC
FE
AI 1
GND
24 V DC
FE
AI 2
GND
24 V DC
FE
AI 3
GND
24 V DC
FE
Connection diagram UR20-4AI-UI-16-DIAG-HD (left 3/4-wire sensor with sensor wiring via electron-
ics, right: 2-wire sensor with sensor wiring via electronics)
6.34 Analogue input module UR20-4AI-UI-16-DIAG-HD