User manual

6 Detailed descriptions of I/O modules | Analogue input module UR20-4AI-UI-16-DIAG
245Manual u-remote1432790000/08/12.2015
Overview of the editable parameters UR20-4AI-UI-16-DIAG
Channel Description Options
1)
Default
Frequency suppression disabled (0) / 50Hz (1) / 60Hz (2) / Average over 16 values (3) disabled
0 ... 3 Channel diagnosis disabled (0) / enabled (1) disabled
0 ... 3 Diag short circiut 24V disabled (0) / enabled (1) disabled
0 ... 3 Diag line break 24V disabled (0) / enabled (1) disabled
0 ... 3 Data format S5 Data format (0) / S7 Data format (1) S7 Data format
0 ... 3 Measurement range
0
 to 20 mA (0) / 4 to 20 mA (1) / 0V to 10V (2) / -10 to 10V (3) /
0 to 5V (4) / -5 to 5V (5) / 1 to 5V (6) / 2 to 10V (7) /disabled (8)
disabled
1) Values in brackets for Modbus-TCP (firmware version 02.00.00 and higher) and EtherCAT