User manual

4 Conguration | Current demand and power supply
23Manual u-remote1432790000/08/12.2015
Current demand
Product group Product I
SYS
I
IN
I
OUT
I
S
I
L
Fieldbus coupler
UR20-FBC-PB-DP 100 mA
UR20-FBC-PN-IRT 116 mA
UR20-FBC-EC 110 mA
UR20-FBC-MOD-TCP, UR20-FBC-EIP 112 mA
UR20-FBC-DN 75mA (+ 15mA from DeviceNet supply)
UR20-FBC-CAN 90mA
Digital
input modules
UR20-4DI-P, UR20-4DI-N 8 mA 6 mA / 18 mA* x
UR20-4DI-P-3W 8mA 12mA / x
UR20-4DI-2W-230V-AC 8mA
UR20-8DI-P-2W, UR20-8DI-P-3W, UR20-8DI-P-3W-HD,
UR20-8DI-N-3W
8 mA 8 mA / 30 mA* x
UR20-16DI-P, UR20-16DI-N 8mA 8 mA / 52 mA* x
UR20-16DI-P-PLC-INT, UR20-16DI-N-PLC-INT 8mA 10 mA / 54 mA* x
UR20-2DI-P-TS 8 mA 6 mA / 12 mA* x
UR20-4DI-P-TS 8 mA 6 mA / 18 mA* x
Digital
output modules
UR20-4DO-P, UR20-4DO-PN-2A, UR20-4DO-N 8 mA 20 mA x
UR20-4DO-P-2A, UR20-4DO-N-2A 8 mA 25 mA x
UR20-8DO-P, UR20-8DO-N 8 mA 35 mA x
UR20-8DO-P-2W-HD 8 mA 35 mA x
UR20-16DO-P, UR20-16DO-P-PLC-INT, UR20-16DO-N,
UR20-16DO-N-PLC-INT
8 mA 25 mA x
UR20-4RO-SSR-255 11 mA
UR20-4RO-CO-255 8 mA 20 mA
Analogue
input modules
UR20-4AI-UI-16, UR20-4AI-UI-16-DIAG, UR20-4AI-UI-16-HD,
UR20-4AI-UI-16-DIAG-HD, UR20-4AI-UI-12
8 mA 25 mA x
UR20-8AI-I-PLC-INT, UR20-4AI-TC-DIAG, UR20-4AI-RTD-DIAG,
UR20-8AI-I-16-HD, UR20-8AI-I-16-DIAG-HD
8 mA 20 mA
Analogue
output modules
UR20-4AO-UI-16, UR20-4AO-UI-16-DIAG 8 mA 85 mA
UR20-4AO-UI-16-HD, UR20-4AO-UI-16-DIAG-HD 8 mA 85 mA
Functional modules
UR20-1CNT-100-1DO 8 mA 35 mA x
UR20-2CNT-100 8 mA 35 mA
UR20-1CNT-500 8mA 20mA x
UR20-2FCNT-100 8 mA 35 mA x
UR20-2PWM-PN-0.5A, UR20-2PWM-PN-2A 8 mA 40 mA x
UR20-1SSI 8mA 25mA x
UR20-1COM-232-485-422
8mA 16 mA
UR20-1COM-SAI-PRO
8mA 17 mA
Safe I/O modules
UR20-4DI-4DO-PN-FSOE, UR20-4DI-4DO-PN-FSPS, UR20-8DI-PN-FSOE,
UR20-8DI-PN-FSPS
8mA 20mA x
I
SYS
Current consumption from the system current path
I
IN
Power consumption from input current path (*all inputs active)
I
OUT
Power consumption from output current path at maximum load
I
S
Current demand of the connected sensors
I
L
Current demand of the connected actuators
x
Must be included when calculating the power supply