219Manual u-remote1432790000/08/12.2015
Technical data UR20-4RO-SSR-255 (Order No. 1315540000)
System data
Data
Process, parameter and diagnostic data depend on the coupler used,
see the table in Section 4.10.
Interface
u-remote system bus
System bus transfer rate
48 Mbps
Outputs
Number
4
Type
SSR / triac
Switching characteristic
closing when the voltage crosses zero, opening when the current crosses zero
Response time
10ms
Minimum switching current
per channel 50mA
Maximum switching current
per channel 1A
per module 4A
Holding current
25mA
Installation
external surge voltage protection circuit recommended for overvoltage category II and III
Switching frequency
up to 20Hz
Short-circuit-proof
no
Defined trip behaviour of the prescribed external fuse
1 A super quick-acting
Module diagnosis
yes
Individual channel diagnosis
no
Max. switching voltage
250V AC, UL: 277 AC
Reactionless
yes
Supply
Supply voltage
24V DC +20 %/-15 %
Current consumption from system current path I
SYS
8mA
General data
Weight (operational status)
83g
For additional general data, see Section 3.4
Overview of the editable parameter UR20-4RO-SSR-255
Channel Description Options
1)
Default
0 ... 3 Substitute value Off (0) / On (1) Off
1) Values in brackets for Modbus-TCP (firmware version 02.00.00 and higher) and EtherCAT